    Product Overview
    The GCK series low-voltage switchgear assembly consists of two parts: Power Distribution Center (PDC) cabinets and Motor Control Center (MCC) cabinets. It is suitable for power users such as power plants, substations, industrial and mining enterprises, and is used in power distribution systems with an AC frequency of 50Hz, a maximum operating voltage of up to 660V, and a maximum operating current of up to 2500A. It serves as power conversion, distribution, and control equipment for power distribution, motor control, lighting, and other electrical distribution applications.
    Share:

    Operating Conditions:

    (1) Altitude: Not exceeding 2000 meters.
    (2) Ambient air temperature: Not higher than +40℃, with an average temperature not exceeding +35℃ within 24 hours; the minimum ambient air temperature shall not be lower than -5℃.
    (3) Atmospheric conditions: Clean air. The relative humidity shall not exceed 50% when the temperature is +40℃, and higher relative humidity is allowed at lower temperatures (e.g., 90% at +20℃).
    (4) The installation site shall be free from fire hazards, explosion risks, severe pollution, chemical corrosion, and severe vibration.
    (5) During installation, the inclination angle relative to the vertical plane shall not exceed 5°.
    (6) This product is suitable for transportation and storage within the temperature range of -25℃ to +55℃. Short-term exposure (not exceeding 24 hours) to a maximum temperature of +65℃ is permitted.
    (7) If the above operating conditions cannot be met, the user shall notify the manufacturer at the time of ordering for negotiation and resolution.

    Technical Parameters

    Rated Operating Voltage (V)

    380

    Rated Insulation Voltage (V)

    660

    Rated Operating Frequency (Hz)

    50

    Rated Operating Current (A) Horizontal Busbar

    630~2500

    Vertical Busbar

    1000

    Rated Short-Time Withstand Current (kA) Horizontal Busbar

    80KA(Effective Value)/1s

    Vertical Busbar

    30KA(Effective Value)/1s

    Rated Peak Withstand Current (kA) Horizontal Busbar

    176KA

    Vertical Busbar

    110KA

    Main Circuit Connector (A)

    200、400

    Power Frequency Withstand Voltage (1 Minute) (V)

    2500

    Electrical Clearance (mm)

    >10

    Creepage Distance (mm)

    >12

    Protection Class

    IP30

    Ordering Instructions

    Operation Mode: Single-sided Operation

    Installation Mode: Freestanding Installation (Wall-independent Installation)

    Wiring Mode: Primary Circuit – Rear Cabinet Wiring; Secondary Circuit – Front and Rear Cabinet Wiring

    Inlet/Outlet Mode: Incoming and outgoing wires can be routed from the top or bottom of the cabinet arbitrarily